B6300 Overcurrent time unit

B6300 Overcurrent time unit

B6300 Overcurrent time unit
  • Plug-in card for B6000
  • Supplied with the actual peak value of three phase currents
  • Preset value activates the time unit
  • Non-essential part of the load will be tripped by an output relay
  • Reset of the time unit in case of current drop


  • Is via Imax logic circuit supplied with the actualpeak value of the three phase currents.

    If the preset value (0,5-2,0 X In) is exceeded thetime unit is activated.

    When the preset time has expired (0,3-30 sec.)either the non-essential part of the load or the generator will be tripped bymeans of the output relay.

    In case of current drop below the preset value, thetime unit will immediately be reset.